Power meter

The power meter computes the electrical quantities of one or three phases from voltage and current channels: RMS values, active, reactive and apparent power, power factor and harmonic distortion. With a DC link and a motor it also computes the converter and motor efficiencies. The results are shown in tables and as a phasor diagram.

Power meter of a three-phase drive

All values are taken over whole periods of the fundamental. If the power meter is linked to a time view whose vertical cursors V1 and V2 are on, only the samples between them are used.

Configuration

Configuration of a power meter

Power Meter

  • Configuration: "Phases" 1 or 3.
  • Voltage inputs:
    • "Input": "Volts", or "Duty cycle (−1…1)" for the duty cycles of a converter; duty cycles are scaled by U_dc / 2.
    • "Connection": "Phase-to-neutral" or "Line-to-line". Duty cycles are always per phase leg.
    • "U_dc (fixed)": DC link voltage for duty cycles, when there is no U_dc channel.
    • "Common-mode removal": subtracts the mean of the three phase voltages from each, e.g. for voltages measured against DC−.
  • Averaging: averages the results over a number of captures (1 … 100, 8 by default); "Reset" starts anew.

Motor

"Include motor" adds speed, torque and the motor efficiencies.

  • Machine: "Pole pairs p"; "R_s", the stator resistance per phase for the copper losses (0: not entered); "Angle is mechanical" if the angle channel is the mechanical angle.
  • Speed: "Source" "None", "Channel", "From angle" or "From frequency" (the synchronous speed; an induction machine runs slower by the slip); "Unit" of a speed channel; "Speed is electrical".
  • Torque: "Source" "None", "Channel" or "Estimate" (three phases only), with the machine constants "ψ_PM", "L_d" and "L_q" for the estimate.

Channel Assignment

"Source" chooses where the data comes from, see data source. Then assign a channel to each role: "U_a", "U_b", "U_c", "I_a", "I_b", "I_c", "U_dc", "I_dc", "Angle", "Speed" and "Torque". With one phase the roles are "U" and "I"; with line-to-line voltages "U_ab", "U_bc" and "U_ca". Unused roles stay at "None".

Status line

The line below the tables shows the number of captures, the analysed range, the number of whole periods, the frequency and where it was taken from, and the averaging, e.g. "Samples: 3, V1–V2, 9 periods, f = 50.0 Hz (angle), avg 4/8". If no whole period is found, it says "No whole period found".

AC table

Columns "a", "b", "c" and "Total" (one phase: "Value"); while frozen, a "Frozen" column is added.

Row Meaning
f Frequency of the fundamental
U_rms, I_rms RMS voltage and current, harmonics included
U₁, I₁ RMS voltage and current of the fundamental
P Active power, mean of u · i
S Apparent power, U_rms · I_rms
Q₁ Reactive power of the fundamental, U₁ · I₁ · sin φ₁
D Distortion power, √(S² − P² − Q₁²)
Q Total reactive power, √(S² − P²)
PF Power factor, P / S
cos φ₁ Displacement factor of the fundamental
φ₁ Phase of U₁ minus phase of I₁
THD_U, THD_I Harmonics 2 … N over the fundamental
THD+N_U, THD+N_I Everything but DC and the fundamental, over the fundamental

Powers are in W, VA and var when the channels are in V and A. Settings → Measurements... chooses the rows ("Rows shown in the AC table:") and the number of harmonics N for THD ("Harmonics N (2..100):", 40 by default).

DC and motor tables

  • DC: "U_dc", "I_dc", "P_dc" and "η_converter", the converter efficiency (DC→AC: P / P_dc; AC→DC: P_dc / P). P and P_dc are positive for power flowing from the DC link to the AC side. Above 100 %, the measured powers do not fit together, e.g. because of offsets or gains.
  • Motor: "Speed", "Torque", "P_mech", "P_loss" (P − P_mech), "P_Cu (est.)" (from R_s), "η_motor" and "η_total".
  • dq (three phases and an angle channel): "u_d", "u_q", "i_d", "i_q", the load angle "δ" of the voltage vector and the angle "γ" of the current vector, both from the q axis.

Diagram

  • Phasors: the fundamentals of the voltages (solid) and currents (dashed) of each phase, with the phase angle φ.
  • dq: the voltage and current vectors u_dq and i_dq on the d and q axes, with the angles δ and γ. "Trajectory" shows the path of the vectors over the capture. The dq diagram needs an angle channel and three phases.

Export

Export writes every value of the tables as Matlab or Scilab variables, e.g. pm_P_a or pm_eta_converter.